Описание

SIMATIC S7-1200, Компактное ЦПУ CPU 1214C DC/DC/DC:

 

  • 14 дискретных входов  =24 В,
  • 10 диск. выходов  =24 В, 2 AI =0 - 10 В,
  • Питание: =20.4-28.8 В,
  • Память для программ/данных: 75 КБ

 

 

 

 

Варанты написания заказного номера:

 

6ES72141AD230XB0

6ES7214-1AD23-0XB0

6ES7 214-1AD23-0XB0

 


***Spare part*** SIMATIC S7-200, CPU 224 Compact unit, DC power supply 14 DI DC/10 DO DC, 8/12 KB progr./8 KB data, PROFIBUS DP expandable

 

 

 

 

Технические данные:

Supply voltage

Rated value (DC)

 

● 24 V DC

Yes

Load voltage L+

● Rated value (DC)

24 V

● permissible range, lower limit (DC)

20.4 V

● permissible range, upper limit (DC)

28.8 V

Input current

Inrush current, max.

12 A; at 28.8 V

from supply voltage L+, max.

700 mA; 110 mA to 700 mA, output current for expansion modules (5 V DC) 660 mA

Encoder supply

24 V encoder supply

● 24 V

Yes; permissible range: 15.4 to 28.8 V

● Short-circuit protection

Yes; electronic at 280 mA

● Output current, max.

280 mA

Power loss

Power loss, typ.

7 W

Memory

Number of memory modules (optional)

1; pluggable memory module, content identical with integral EEPROM; can additionally store recipes, data logs and other files

Work memory

● integrated (for program)

12 kbyte; 8 KB with active run-time edit

● integrated (for data)

8 kbyte

Backup

● present

Yes; Program: Entire program maintenance-free on integral EEPROM, programmable via CPU; data: Entire DB 1 loaded from PG/PC maintenance-free on integral EEPROM, current values of DB 1 in RAM, retentive memory bits, timers, counters, etc. maintenance-free via high-performance capacitor; optional battery for long-term buffering

Battery

Backup battery

● Backup time, max.

100 h; (min. 70 h at 40 °C); 200 days (typ.) with optional battery module

CPU processing times

for bit operations, max.

0.22 µs

Counters, timers and their retentivity

S7 counter

● Number

256

Retentivity

— adjustable

Yes; via high-performance capacitor or battery

— lower limit

1

— upper limit

256

Counting range

— lower limit

0

— upper limit

32 767

S7 times

● Number

256

Retentivity

— adjustable

Yes; via high-performance capacitor or battery

— upper limit

64

Time range

— lower limit

1 ms

— upper limit

54 min; 4 timers: 1 ms to 30 s; 16 timers: 10 ms to 5 min; 236 timers: 100 ms to 54 min

Data areas and their retentivity

Flag

● Number, max.

32 byte

● of which retentive with battery

0 to 255, via high-performance capacitor or battery, adjustable

● of which retentive without battery

0 to 112 in EEPROM, adjustable

Hardware configuration

Number of expansion units, max.

7; Only expansion modules of the S7-22x series can be used. Due to the limited output current, the use of expansion modules may be limited.

connectable programming devices/PCs

SIMATIC PG/PC, standard PC

Expansion modules

● Analog inputs/outputs, max.

35; max. 28 inputs and 7 outputs (EM) or max. 0 inputs and 14 outputs (EM)

● Digital inputs/outputs, max.

168; max. 94 inputs and 74 outputs (CPU + EM)

● AS-Interface inputs/outputs, max.

62; AS-Interface A/B slaves (CP 243-2)

Digital inputs

Number of digital inputs

14

Source/sink input

Yes; optionally, per group

Input voltage

● Rated value (DC)

24 V

● for signal "0"

0 to 5 V

● for signal "1"

min. 15 V

Input current

● for signal "1", typ.

2.5 mA

Input delay (for rated value of input voltage)

for standard inputs

— parameterizable

Yes; all

— at "0" to "1", min.

0.2 ms

— at "0" to "1", max.

12.8 ms

for interrupt inputs

— parameterizable

Yes; I 0.0 to I 0.3

for technological functions

— parameterizable

Yes; (E 0.0 to E 1.5) 30 kHz

Cable length

● shielded, max.

500 m; Standard input: 500 m, high-speed counters: 50 m

● unshielded, max.

300 m; not for high-speed signals

Digital outputs

Number of digital outputs

10; Transistor

Short-circuit protection

No; to be provided externally

Limitation of inductive shutdown voltage to

1 W

Switching capacity of the outputs

● with resistive load, max.

0.75 A

● on lamp load, max.

5 W

Output voltage

● for signal "1", min.

20 V DC

Output current

● for signal "1" rated value

750 mA

● for signal "0" residual current, max.

10 µA

Output delay with resistive load

● "0" to "1", max.

15 µs; of the standard outputs, max. (Q 0.2 to Q 1.1) 2 µs; of the pulse outputs, max. (Q 0.0 to Q 0.1) 2 µs

● "1" to "0", max.

130 µs; of the standard outputs, max. (Q 0.2 to Q 1.1) 10 µs; of the pulse outputs, max. (Q 0.0 to Q 0.1) 10 µs

Parallel switching of two outputs

● for uprating

Yes

Switching frequency

● of the pulse outputs, with resistive load, max.

20 kHz; Q0.0 to Q0.1

Total current of the outputs (per group)

all mounting positions

— up to 40 °C, max.

6 A

horizontal installation

— up to 55 °C, max.

6 A

Relay outputs

● Number of relay outputs

0

● Number of relay outputs, integrated

0

Cable length

● shielded, max.

500 m

● unshielded, max.

150 m

Analog inputs

Number of analog potentiometers

2; Analog potentiometer; resolution 8 bit

Encoder

Connectable encoders

● 2-wire sensor

Yes

— permissible quiescent current (2-wire sensor), max.

1 mA

1. Interface

Interface type

Integrated RS 485 interface

Physics

RS 485

Protocols

● MPI

Yes; As MPI slave for data exchange with MPI masters (S7-300/S7-400 CPUs, OPs, TDs, Push Button Panels); S7-200-internal CPU/CPU communication is possible in the MPI network with restrictions; transmission rates: 19.2/187.5 kbit/s

● PPI

Yes; with PPI protocol for program functions, HMI functions (TD 200, OP), S7-200-internal CPU/CPU communication ; transmission rates 9.6/19.2/187.5 kbit/s

● serial data exchange

Yes; As freely programmable interface with interrupt facility for serial data exchange with third-party devices with ASCII protocol transfer rates: 1.2 / 2.4 / 4.8 / 9.6 / 19.2 / 38.4 / 57.6 / 115.2 kbps; the PC/PPI cable can also be used as RS 232/RS 485 converter

MPI

● Transmission rate, min.

19.2 kbit/s

● Transmission rate, max.

187.5 kbit/s

Integrated Functions

Number of counters

6; High-speed counters (30 kHz each), 32 bit (incl. sign), can be used as up/down counters or for connecting 2 incremental encoders with 2 pulse trains offset by 90° (max. 20 kHz (A/B counters)); parameterizable enable and reset input; interrupt facilities (incl. call of subroutine with any content) when the setpoint is reached; reversal in counting direction, etc.

Counting frequency (counter) max.

30 kHz

Number of alarm inputs

4; 4 rising edges and/or 4 falling edges

Number of pulse outputs

2; High-speed outputs, 20 kHz, with interrupt option; pulse-width and frequency modulation option

Limit frequency (pulse)

20 kHz

Potential separation

Potential separation digital inputs

● between the channels

Yes

● between the channels, in groups of

6 and 8

Potential separation digital outputs

● between the channels

Yes; Optocoupler

● between the channels, in groups of

5

Permissible potential difference

between different circuits

500 V DC between 24 V DC and 5 V DC

Degree and class of protection

Degree of protection acc. to EN 60529

 

● IP20

Yes

Ambient conditions

Ambient temperature during operation

● horizontal installation, min.

0 °C

● horizontal installation, max.

55 °C

● vertical installation, min.

0 °C

● vertical installation, max.

45 °C

Air pressure acc. to IEC 60068-2-13

● permissible range, lower limit

860 hPa

● permissible range, upper limit

1 080 hPa

Relative humidity

● Operation, min.

5 %

● Operation, max.

95 %; RH class 2 in accordance with IEC 1131-2

Configuration

Programming

● Command set

Bit logic instructions, compare instructions, timer instructions, counter instructions, clock instructions, transmissions instructions, table instructions, logic instructions, shift and rotate instructions, conversion instructions, program control instructions, interrupt and communications instructions, logic stack instructions, integer maths, floating-point math instructions, numerical functions

● Program processing

free cycle (OB 1), interrupt-controller, time-controlled (1 to 255 ms)

● Program organization

1 OB, 1 DB, 1 SDB subroutines with/without parameter transfer

● Number of subroutines, max.

64

Programming language

— LAD

Yes

— FBD

Yes

— STL

Yes

Know-how protection

● User program protection/password protection

Yes; 3-stage password protection

Connection method

Plug-in I/O terminals

Yes

Dimensions

Width

120.5 mm

Height

80 mm

Depth

62 mm

Weights

Weight, approx.

360 g

 

Характеристики

Основные
Производитель  Siemens AG
Вес0.36 (кг)
Гарантийный срок  12 (мес)

Информация для заказа

  • Цена: 880