1734-EP24DC Allen-Bradley блок питания POINT I/O

Описание
Блок питания для серии POINT I/O:
- Для серии 1734
- Вход (номинальный) =24В
- Выход при горизонтальном установке: 1.3 A при при входном напряжении 19.2…28.8V
- Выход при вертикальной установке: 1 A при входном напряжении 10…28.8V
- Может запитать от 4 до 17 модулей, в зависимости от их энергопотребления
Варианты решения заказного номера:
1734EP24DC
1734-EP24DC
POINT I/O™ 24V DC Expansion Power Supply – 1734-EP24DC
Технические данные:
I/O module capacity 4...17 modules, depending on current rating of each module
Input voltage rating 24V DC nominal
10…28.8V DC range
Field side power requirements 24V DC (+20% = 28.8V DC max) @ 400 mA max
Inrush current, max 6 A for 10 ms
Indicators 1 green field power status indicator
1 green 5V system power indicator
POINTBus™ output current
Horizontal mounting – 1 A @ 10…19.2V input;
1.3 A @ 19.2…28.8V input
Vertical mounting – 1 A @ 10…28.8V input
Input overvoltage protection Reverse polarity protected
Interruption Output voltage will stay within specifications when input drops out for 10 ms @
10V with maximum load.
Module location Between I/O modules in 1734 system
Breaks field power bus
Limitations Use with POINT I/O™ Adapters only
Dimensions (H x W x D), approx 76.2 x 25.4x 133.4 mm
(3.0 x 1.0 x 5.25 in)
Weight, approx 120 g (4.3 oz)
Terminal base screw torque 0.6 N•m (7 lb-in)
Power Consumption, max 9.8 W @ 28.8V DC
Power dissipation, max 3.0 W @ 28.8V DC
Thermal dissipation, max 10.0 BTU/hr @ 28.8V DC
Field power bus supply voltage, nom 24V DC
Field power bus voltage range 10...28.8V DC
Field power bus supply current, max 10 A
Isolation voltage 50V continuous, tested to withstand 2600V DC for 60 s
Enclosure type rating None (open-style)
North American temp code T4A
ATEX temp code T4
Conductor size
0.324…2.08 mm2 (22…14 AWG) solid or stranded copper wire rated @ 75 °C
(167 °F) or greater
3/64 inch (1.2 mm) insulation maximum
Conductor category(1)
(1) Use this Conductor Category information for planning conductor routing as described in the appropriate System Level
Installation Manual. Also refer to Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1, for
more information.
2 – on power ports
Temperature, operating
IEC 60068-2-1 (Test Ad, operating cold),
IEC 60068-2-2 (Test Bd, operating dry heat),
IEC 60068-2-14 (Test Nb, operating thermal shock):
-20…+55 °C (-4…+131 °F)
Temperature, storage
IEC 60068-2-1 (Test Ab, unpackaged nonoperating cold),
IEC 60068-2-2 (Test Bb, unpackaged nonoperating dry heat),
IEC 60068-2-14 (Test Na, unpackaged nonoperating thermal shock):
-40…+85 °C (-40…+185 °F)
Temperature, surrounding air, max. 55 °C (131 °F)
Relative humidity IEC 60068-2-30 (Test Db, unpackaged nonoperating damp heat):
5…95% noncondensing
Vibration IEC60068-2-6 (Test Fc, operating):
5 g @ 10...500 Hz
Shock, operating IEC 60068-2-27 (Test Ea, unpackaged shock):
30 g
Shock, nonoperating IEC 60068-2-27 (Test Ea, unpackaged shock):
50 g
Emissions IEC 61000-6-4
ESD immunity
IEC6100-4-2:
6 kV contact discharges
8 kV air discharges
Radiated RF immunity
IEC 61000-4-3:
10V/m with 1 kHz sine-wave 80% AM from 80...2000 MHz
10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz
10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz
10V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz
EFT/B immunity
IEC 61000-4-4:
±2 kV at 5 kHz on power ports
±2 kV at 5 kHz on signal ports
Surge transient immunity IEC 61000-4-5:
±1 kV line-line (DM) and ±2 kV line-earth (CM) on signal ports
Conducted RF immunity IEC61000-4-6:
10V rms with 1 kHz sine-wave 80% AM from 150 kHz to 80 MHz
Характеристики
Основные | |
---|---|
Производитель | Allen-Bradley |
Страна производитель | США |
Вес | 0.1 (кг) |
Гарантийный срок | 12 (мес) |
Информация для заказа
- Цена: 138 €